(2) Parallel Approach Only. If only a parallel approach is possible, operable parts of controls shall be placed as follows:

(a) Reach Depth Not More Than 10 in (255 mm). Where the reach depth to the operable parts of all controls as measured from the vertical plane perpendicular to the edge of the unobstructed clear floor space at the farthest protrusion of the automated teller machine or surround is not more than 10 in (255 mm), the maximum height above the finished floor or grade shall be 54 in (1370 mm).

(b) Reach Depth More Than 10 in (255 mm). Where the reach depth to the operable parts of any control as measured from the vertical plane perpendicular to the edge of the unobstructed clear floor space at the farthest protrusion of the automated teller machine or surround is more than 10 in (255 mm), the maximum height above the finished floor or grade shall be as follows:

Reach  Depth   Maximum    Height 
 In    Mm   In   Mm 
10 255 54 1370
11 280 53 1/2 1360
12 305 53 1345
13 330 52 1/2 1335
14 355 51 1/2 1310
15 380 51 1295
16 405 50 1/2 1285
17 430 50 1270
18 455 49 1/2 1255
19 485 49 1245
20 510 48 1/2 1230
21 535 47 1/2 1205
22 560 47 1195
23 585 46 1/2 1180
24 610 46 1170

 