2010 ADA Standards for Accessible Design Pocket Guide
105.2.5 NFPA.
Copies of the referenced standards may be obtained from the National Fire Protection Association, 1 Batterymarch Park, Quincy, Massachusetts 02169‒7471, (http://www.nfpa.org).
NFPA 72 National Fire Alarm Code, 1999 Edition (see 702.1 and 809.5.2).
NFPA 72 National Fire Alarm Code, 2002 Edition (see 702.1 and 809.5.2).
Advisory 105.2.5 NFPA. NFPA 72‒1999 and NFPA 72‒2002 address the application, installation, performance, and maintenance of protective signaling systems and their components. The NFPA 72 incorporates Underwriters Laboratory (UL) 1971 by reference. The standard specifies the characteristics of audible alarms, such as placement and sound levels. However, Section 702 of these requirements limits the volume of an audible alarm to 110 dBA, rather than the maximum 120 dBA permitted by NFPA 72‒1999.
NFPA 72 specifies characteristics for visible alarms, such as flash frequency, color, intensity, placement, and synchronization. However, Section 702 of this document requires that visual alarm appliances be permanently installed. UL 1971 specifies intensity dispersion requirements for visible alarms. In particular, NFPA 72 requires visible alarms to have a light source that is clear or white and has polar dispersion complying with UL 1971.
User Comments/Questions
Add Comment/Question