605.2 Height and Depth.

Urinals shall be the stall-type or the wall-hung type with the rim 17 inches (430 mm) maximum above the finish floor or ground. Urinals shall be 13½ inches (345 mm) deep minimum measured from the outer face of the urinal rim to the back of the fixture. [S.H. 4.18.2]

Figure (a) is an elevation drawing of a wall hung type having the urinal rim 17 inches (430 mm) maximum above the floor with a minimum depth of 13 1/2 inches (350 mm) measured from the outer face of the rim to the back of the fixture.
Figure (b) is an elevation drawing of a stall (floor) type having a minimum depth of 13 1/2 inches (350 mm) measured from the outer face of the rim to the back of the fixture.

Figure 605.2 Height and Depth of Urinals