2010 California Standards for Accessible Design (excerpts relating to Safe Harbors only)
SECTION 1133B
GENERAL ACCESSIBILITY FOR ENTRANCES, EXITS AND PATHS OF TRAVEL
1133B.2 Doors.
1133B.2.4 Floor level at doors. Regardless of the occupant load, there shall be a floor or landing on each side of a door.
1133B.2.4.2 Maneuvering clearances at doors. Minimum maneuvering clearances at doors shall be as shown in Figures11B-26A,11B-26B and11B-26C.The floor or ground area within the required clearances shall be level and clear. …
FIGURE 11B-26A -- LEVEL MANEUVERING CLEARANCE AT DOORS ‡‡
FIGURE 11B-26C -- LEVEL MANEUVERING CLEARANCE AT DOORS ‡‡
ETA Editor's Note
The requirements of 2010 CBC 1133B.2.4.2 are more stringent than 1991 ADAAG 4.13.6. They are less stringent than 2013 CBC 404.2.4.1 for swinging doors approached from the hinge side on the "push" side [2010 CBC Fig. 11B-26A(b)], and 2013 CBC 404.2.4.2 for sliding doors and folding doors approached from the pocket/hinge side [2010 CBC Figs. 11B-26C(e) & (h)].