2013 California Standards for Accessible Design Pocket Guide
[F] 907.5.2 Alarm notification appliances. ...
[F] 907.5.2.3 Visible alarms. Visible alarm notification appliances shall be provided in accordance with Sections 907.5.2.3.1 through 907.5.2.3.5.
Exceptions:
1. In other than Group I-2 and I-2.1, visible alarm notification appliances are not required in alterations, except where an existing fire alarm system is upgraded or replaced, or a new fire alarm system is installed.
2. Visible alarm notification appliances shall not be required in enclosed exit stairways, exterior exit stairs and exterior exit ramps.
3. Visible alarm notification appliances shall not be required in elevator cars.
[F] 907.5.2.3.1 Public and common use areas. Visible alarm notification appliances shall be provided in public use areas and common use areas, including but not limited to:
-
Sanitary facilities including restrooms, bathrooms and shower rooms
-
Music practice rooms
-
Band rooms
-
Multipurpose rooms
-
Occupational shops
-
Occupied rooms where ambient noise impairs hearing of the fire alarm
-
Meeting rooms
-
Occupied rooms where ambient noise impairs hearing of the fire alarm
-
Lobbies
-
Meeting rooms
-
Classrooms
[F] 907.5.2.3.2 Employee work areas. Where employee work areas have audible alarm coverage, the notification appliance circuits serving the employee work areas shall be initially designed with a minimum of 20-percent spare capacity to account for the potential of adding visible notification appliances in the future to accommodate hearing impaired employee(s).
[F] 907.5.2.3.3 Groups R-1 and R-2.1. Group R-1 and R-2.1 dwelling units or sleeping units in accordance with Table 907.5.2.3.3 shall be provided with a visible alarm notification appliance, activated by both the in-room smoke alarm and the building fire alarm system.
[F] TABLE 907.5.2.3.3 VISIBLE ALARMS
NUMBER OF SLEEP UNITS |
SLEEPING ACCOMMODATIONS WITH VISIBLE ALARMS |
---|---|
6 to 25 |
2 |
26 to 50 |
4 |
51 to 75 |
7 |
76 to 100 |
9 |
101 to 150 |
12 |
151 to 200 |
14 |
201 to 300 |
17 |
301 to 400 |
20 |
401 to 500 |
22 |
501 to 1,000 |
5% of total |
1,001 and over |
50 plus 3 for each 100 over 1,000 |
[F] 907.5.2.3.4 Group R-2. In Group R-2 occupancies required by Section 907 to have a fire alarm system, all dwelling units and sleeping units shall be provided with the capability to support visible alarm notification appliances in accordance with NFPA 72. Such capability shall be permitted to include the potential for future interconnection of the building fire alarm system with the unit smoke alarms, replacement of audible appliances with combination audible/visible appliances, or future extension of the existing wiring from the unit smoke alarm locations to required locations for visible appliances.
907.5.2.3.5 Groups R-2.1, R-3.1 and R-4. Protective social care facilities which house persons who are hearing impaired, shall be provided with notification appliances for the hearing impaired installed in accordance with NFPA 72 and which shall activated upon initiation of the fire alarm system or the smoke alarms.
ETA Editor's Note
Remainder of California Building Code Chapter 9, not adopted by Division of the State Architect - Access Compliance (DSA-AC), omitted. To see the entire Chapter, consult California Code of Regulations, Title 24, Part 2 - 2013 California Building Code (2013 CBC), available for purchase from International Code Council (http://www.iccsafe.org/).
User Comments/Questions
Add Comment/Question