11B-806.2.3.1 Personal lift device floor space.

There shall be a clear space under the bed for the use of a personal lift device. The clear space shall extend under the bed parallel to the long side and be adjacent to an accessible route. The clear space shall extend to points horizontally 30 inches (762 mm), vertically 7 inches (178 mm) and not more than 12 inches (305 mm) from the head and foot end of the bed.

ETA Editor's Note

The clearance prescribed for a personal lift device at CBC 11B-806.2.3.1 is not required by 2010 ADAS.