2019 California Standards for Accessible Design Guide (effective January 1, 2020 with July 1, 2021 amendments)
11B-308.1 General.
Reach ranges shall comply with Section 11B-308.
Children's Reach Ranges |
|||
---|---|---|---|
Forward or Side Reach |
Ages 3 and 4 | Ages 5 through 8 |
Ages 9 through 12 |
High (maximum) |
36 in (915 mm) |
40 in (1015 mm) |
44 in (1120 mm) |
Low (minimum) |
20 in (510 mm) |
18 in (455 mm) |
16 in (405 mm) |
11B-308.1.1 Electrical switches.
Controls and switches intended to be used by the occupant of a room or area to control lighting and receptacle outlets, appliances or cooling, heating and ventilating equipment, shall comply with Section 11B-308 except the low reach shall be measured to the bottom of the outlet box and the high reach shall be measured to the top of the outlet box.
11B-308.1.2 Electrical receptacle outlets.
Electrical receptacle outlets on branch circuits of 30 amperes or less and communication system receptacles shall comply with Section 11B-308 except the low reach shall be measured to the bottom of the outlet box and the high reach shall be measured to the top of the outlet box.