11B-205 Operable parts
11B-205.1 General.
Operable parts on accessible elements, accessible routes, and in accessible rooms and spaces shall comply with Section 11B-309.
Exceptions:
1. Operable parts that are intended for use only by service or maintenance personnel shall not be required to comply with Section 11B-309.
2. Electrical or communication receptacles serving a dedicated use shall not be required to comply with Section 11B-309.
3. Reserved.
[2010 ADA Standards] 3. Where two or more outlets are provided in a kitchen above a length of counter top that is uninterrupted by a sink or appliance, one outlet shall not be required to comply with 309.
ETA Editor's Note
The ADA requirement included at Section 11B-205.1 Exception 3 is provided for information only. The CBC scoping requirement is more inclusive.
4. Floor electrical receptacles shall not be required to comply with Section 11B-309.
5. HVAC diffusers shall not be required to comply with Section 11B-309.
6. Except for light switches, where redundant controls are provided for a single element, one control in each space shall not be required to comply with Section 11B-309.
7. Cleats and other boat securement devices shall not be required to comply with Section 11B-309.3.
8. Exercise machines and exercise equipment shall not be required to comply with Section 11B-309.
9. In residential dwelling units with mobility features where receptacles are provided in a kitchen at a corner work surface, one receptacle shall be located 36 inches (915 mm) from either wall at the inside corner.