2022 California Standards for Accessible Design Guide (effective January 1, 2023)
11B-215 Fire alarm systems and carbon monoxide alarm systems
[2010 ADA Standards] 215 Fire Alarm Systems
ETA Editor’s Note
The CBC includes carbon monoxide alarm systems. Therefore, the CBC is more inclusive.
11B-215.1 General.
Where fire alarm systems and carbon monoxide alarm systems provide audible alarm coverage, alarms shall comply with Section 11B-215.
[2010 ADA Standards] 215.1 General. Where fire alarm systems provide audible alarm coverage, alarms shall comply with 215.
Exception: In existing facilities, visible alarms for fire alarm systems shall not be required except where an existing fire alarm system is upgraded or replaced, or a new fire alarm system is installed.
ETA Editor’s Note
The CBC includes carbon monoxide alarm systems. Therefore, the CBC is more inclusive.
11B-215.2 Public and common use areas.
Alarms in public use areas and common use areas shall comply with Chapter 9, Section 907.5.2.3.1.
[2010 ADA Standards] 215.2 Public and Common Use Areas. Alarms in public use areas and common use areas shall comply with 702.
11B-215.3 Employee work areas.
Where employee work areas have audible alarm coverage, the wiring system shall be designed so that visible alarms complying with Chapter 9, Section 907.5.2.3.1 Exception can be integrated into the alarm system.
[2010 ADA Standards] 215.3 Employee Work Areas. Where employee work areas have audible alarm coverage, the wiring system shall be designed so that visible alarms complying with 702 can be integrated into the alarm system.
11B-215.4 Transient lodging.
Guest rooms required to comply with Section 11B-224.4 shall provide fire alarms complying with Chapter 9, Section 907.5.2.3.2, and carbon monoxide alarms, where provided, complying with Chapter 9, Section 915.
[2010 ADA Standards] 215.4 Transient Lodging. Guest rooms required to comply with 224.4 shall provide alarms complying with 702.
11B-215.5 Residential facilities.
Where provided in residential dwelling units required to comply with Section 11B-809.5, fire alarms shall comply with Chapter 9, Section 907.5.2.3.3 and carbon monoxide alarms shall comply with Chapter 9, Section 915.
[2010 ADA Standards] 215.5 Residential Facilities. Where provided in residential dwelling units required to comply with 809.5, alarms shall comply with 702.
ETA Editor's Note
The ADA requirements included at Sections 11B-215.2 through 11B-215.5 are provided for information only. 2010 ADA Standards Section 702 refers to NFPA 72 for the scoping of visible alarms, while CBC Section 907.5.2.3 contains specific scoping.
User Comments/Questions
Add Comment/Question