2022 California Standards for Accessible Design Guide (effective January 1, 2023)
SECTION 1015 GUARDS
1015.2 Where required.
Guards shall be located along open-sided walking surfaces, including mezzanines, equipment platforms, aisles, stairs, ramps and landings that are located more than 30 inches (762 mm) measured vertically to the floor or grade below at any point within 36 inches (914 mm) horizontally to the edge of the open side. Guards shall be adequate in strength and attachment in accordance with Section 1607.8.
Exception: Guards are not required for the following locations:
- On the loading side of loading docks or piers.
- On the audience side of stages and raised platforms, including stairs leading up to the stage and raised platforms.
- On raised stage and platform floor areas, such as runways, ramps and side stages used for entertainment or presentations.
- At vertical openings in the performance area of stages and platforms.
- At elevated walking surfaces appurtenant to stages and platforms for access to and utilization of special lighting or equipment.
- Along vehicle service pits not accessible to the public.
- In assembly seating areas at cross aisles in accordance with Section 1029.12.
- On the loading side of station platforms on fixed guideway transit or passenger rail systems.
- Elevated facility observation station access hatches at detention facilities.
1015.3 Height.
Required guards shall not be less than 42 inches (1067 mm) high, measured vertically as follows:
- From the adjacent walking surfaces.
- On stairways and stepped aisles, from the line connecting the leading edges of the tread nosings.
- On ramps and ramped aisles, from the ramp surface at the guard.
Exceptions:
- For occupancies in Group R-3, and within individual dwelling units in occupancies in Group R-2, guards on the open sides of stairs shall have a height not less than 34 inches (864 mm) measured vertically from a line connecting the leading edges of the treads.
- For occupancies in Group R-3, and within individual dwelling units in occupancies in Group R-2, where the top of the guard serves as a handrail on the open sides of stairs, the top of the guard shall be not less than 34 inches (864 mm) and not more than 38 inches (965 mm) measured vertically from a line connecting the leading edges of the treads.
- The guard height in assembly seating areas shall comply with Section 1029.17 as applicable.
- Along alternating tread devices and ship’s ladders, guards where the top rail serves as a handrail shall have height not less than 30 inches (762 mm) and not more than 34 inches (864 mm), measured vertically from the leading edge of the device tread nosing.
- In Group F occupancies where exit access stairways serve fewer than three stories and such stairways are not open to the public, and where the top of the guard also serves as a handrail, the top of the guard shall be not less than 34 inches (864 mm) and not more than 38 inches (965 mm) measured vertically from a line connecting the leading edges of the treads.
ETA Editor's Note
Sections from California Building Code Chapter 10 that are not adopted by the Division of the State Architect - Access Compliance (DSA-AC) have been omitted. To see the entire Chapter, consult California Code of Regulations, Title 24, Part 2 - 2022 California Building Code (2022 CBC), available for purchase from the International Code Council (http://www.iccsafe.org).