608.3 Grab Bars.

Grab bars shall comply with 609 and shall be provided in accordance with 608.3. Where multiple grab bars are used, required horizontal grab bars shall be installed at the same height above the finish floor. [ECTCR UFAS 4.21.4, Fig. 37, 4.34.5.5(3), Fig. 49]

EXCEPTIONS: 1. Grab bars shall not be required to be installed in a shower located in a bathing facility for a single occupant accessed only through a private office, and not for common use or public use provided that reinforcement has been installed in walls and located so as to permit the installation of grab bars complying with 608.3.

2. In residential dwelling units, grab bars shall not be required to be installed in showers located in bathing facilities provided that reinforcement has been installed in walls and located so as to permit the installation of grab bars complying with 608.3.

608.3.1 Transfer Type Shower Compartments.

In transfer type compartments, grab bars shall be provided across the control wall and back wall to a point 18 inches (455 mm) from the control wall.

Plan view shows a grab bar that extends across the control wall and the back wall to a point 18 inches (455 mm) from the control wall.

Figure 608.3.1 Grab Bars for Transfer Type Showers

608.3.2 Standard Roll-In Type Shower Compartments.

Where a seat is provided in standard roll-in type shower compartments, grab bars shall be provided on the back wall and the side wall opposite the seat. Grab bars shall not be provided above the seat. Where a seat is not provided in standard roll-in type shower compartments, grab bars shall be provided on three walls. Grab bars shall be installed 6 inches (150 mm) maximum from adjacent walls. [ECTCR UFAS 4.21.4, Fig. 37(b), 4.34.5.5(3), Fig. 49(b)]

Figure (a) is a plan view of a shower without a seat.  Grab bars are provided on three walls that are 6 inches (150 mm) maximum from the adjacent wall. 
Figure (b) is a plan view of a shower with a seat on one side wall.  Grab bars are provided on the opposite side wall and the back wall.  The back wall grab bar does not extend over the seat.  The grab bars are 6 inches (150 mm) maximum from the adjacent wall.

Figure 608.3.2 Grab Bars for Standard Roll-In Type Showers

608.3.3 Alternate Roll-In Type Shower Compartments.

In alternate roll-in type shower compartments, grab bars shall be provided on the back wall and the side wall farthest from the compartment entry. Grab bars shall not be provided above the seat. Grab bars shall be installed 6 inches (150 mm) maximum from adjacent walls.

This figure shows an alternate roll-in shower with a seat.  A grab bar extends on the wall opposite the seat and is 6 inches (150 mm) maximum from adjacent walls.  Another grab bar is mounted on the side wall adjacent to the seat; this grab bar does not extend over the seat and is 6 inches (150 mm) maximum from the back wall.

Figure 608.3.3 Grab Bars for Alternate Roll-In Type Showers