Withdrawn Technical Assistance: Common ADA Errors and Omissions in New Construction and Alterations
Error/Omission:
Adequate maneuvering clearance is not provided at doors, including doors to accessible toilet stalls.
Result:
A person using a wheelchair cannot open the door without a clear level area in front of and adjacent to the door that provides a place to maneuver.
Requirement:
4.13.6 Maneuvering Clearances at Doors. Minimum maneuvering clearances at doors that are not automatic or power-assisted shall be as shown in Fig. 25. The floor or ground area within the required clearances shall be level and clear.
4.17.5* Doors. Toilet stall doors, including door hardware, shall comply with 4.13. If toilet stall approach is from the latch side of the stall door, clearance between the door side of the stall and any obstruction may be reduced to a minimum of 42 in (1065 mm) (Fig. 30).
* Asterisk denotes that related, non-mandatory material is in the Appendix to the Standards.