704.8 Allowable area of openings.
The maximum area of unprotected or protected openings permitted in an exterior wall in any story shall not exceed the values set forth in Table 704.8. Where both unprotected and protected openings are located in the exterior wall in any story, the total area of the openings shall comply with the following formula:
where:
A = Actual area of protected openings, or the equivalent area of protected openings, Ae (see Section 704.7).
a = Allowable area of protected openings.
Au = Actual area of unprotected openings.
au = Allowable area of unprotected openings.
TABLE 704.8 MAXIMUM AREA OF EXTERIOR WALL OPENINGSa
Classification of opening | FIRE SEPARATION DISTANCE (feet) | |||||||
0 to 3 e,h | Greater that 3 to 5b | Greater than 5 to 10d,f | Greater than 10 to 15c,d,f | Greater than 15 to 20c,f | Greater than 20 to 25c,f | Greater than 25 to 30c,f | Greater than 30 | |
Unprotected |
Not Permitted g |
Not Permitted b,g |
10%g | 15%g | 25%g | 45%g | 70%g |
No Limit |
Protected |
Not Permitted |
15% | 25% | 45% | 75% |
No Limit |
No Limit |
No Limit |
For SI: 1 foot = 304.8 mm.
a. Values given are percentage of the area of the exterior wall.
b. For occupancies in Group R-3, as applicable in Section 101.2, the maximum percentage of unprotected and protected exterior wall openings shall be 25 percent.
c. The area of openings in an open parking structure with a fire separation distance of greater than 10 feet shall not be limited.
d. For occupancies in Group H-2 or H-3, unprotected openings shall not be permitted for openings with a fire separation distance of 15 feet or less.
e. For requirements for fire walls for buildings with differing roof heights, see Section 705.6.1.
f. The area of unprotected and protected openings is not limited for occupancies in Group R-3, as applicable in Section 101.2, with a fire separation distance greater than 5 feet.
g. Buildings whose exterior bearing wall, exterior nonbearing wall and exterior structural frame are not required to be fire-resistance rated shall be permitted to have unlimited unprotected openings.
h. Includes accessory buildings to Group R-3 as applicable in Section 101.2.
704.8.1 Automatic sprinkler system.
In buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, the maximum allowable area of unprotected openings in occupancies other than Groups H-1, H-2 and H-3 shall be the same as the tabulated limitations for protected openings.
704.8.2 First story.
In occupancies other than Group H, unlimited unprotected openings are permitted in the first story of exterior walls facing a street that have a fire separation distance of greater than 15 feet (4572 mm), or facing an unoccupied space. The unoccupied space shall be on the same lot or dedicated for public use, shall not be less than 30 feet (9144 mm) in width, and shall have access from a street by a posted fire lane in accordance with the International Fire Code.
User Comments/Questions
Add Comment/Question