Excerpts from 2000 INTERNATIONAL BUILDING CODE®

Note: This excerpt is only a portion of a larger, Referenced Standards document and out of context may not include all information needed for use. Also, it may not reflect the most current building code requirements. The Referenced Standard, in its entirety, may be available for purchase from the International Code Council at http://shop.iccsafe.org.

SECTION 1004
EXIT ACCESS

1004.2.1 Exit or exit access doorways required.

Two exits or exit access doorways from any space shall be provided where one of the following conditions exists:

  1. The occupant load of the space exceeds the values in Table 1004.2.1.

  2. The common path of egress travel exceeds the limitations of Section 1004.2.5.

Exception: Exit access doors required by Section 1004.2.3.2 for Group I-2 occupancies.

TABLE 1004.2.1
SPACES WITH ONE MEANS OF EGRESS

OCCUPANCY MAXIMUM OCCUPANT LOAD
A,B,E,F,M,U 50
H-1,H-2,H-3 3
H-4,H-5,I-1,I-3,I-4,R 10
S 30