Hello. Please sign in!

(4) Special technical provisions for alterations to existing buildings or facilities:

(a) Ramps. Curb ramps and ramps to be constructed on existing sites or in existing buildings or facilities may have slopes and rises as shown in Table 2 if space limitations prohibit the use of a 1:12 slope or less.

Table 2 -- Allowable Ramp Dimensions for Construction in Existing Sites, Buildings, and Facilities

Slope* Maximum Rise Maximum Run
Steeper than 1:10 but no steeper than 1:8 3 in (75 mm) 2 ft (0.6 m)
Steeper than 1:12 but no steeper than 1:10 6 in (150 mm) 5 ft (1.5 m)

* A slope steeper than 1:8 not allowed.

(b) Stairs. Full extension of stair handrails shall not be required in alterations where such extensions would be hazardous or impossible due to plan configuration.

(c) Elevators.

(i) If a safety door edge is provided in existing automatic elevators, then the automatic door reopening devices may be omitted (see 4.10.6).

(ii) Where existing shaft or structural elements prohibit strict compliance with 4.10.9, then the minimum floor area dimensions may be reduced by the minimum amount necessary, but in no case shall they be less than 48 in by 48 in (1220 mm by 1220 mm).

(d) Doors.

(i) Where existing elements prohibit strict compliance with the clearance requirements of 4.13.5, a projection of 5/8 in (16 mm) maximum will be permitted for the latch side door stop.

(ii) If existing thresholds measure 3/4 in (19 mm) high or less, and are beveled or modified to provide a beveled edge on each side, then they may be retained.

(e) Toilet rooms. Where alterations to existing facilities make strict compliance with 4.22 and 4.23 structurally impracticable, the addition of one "unisex" toilet per floor containing one water closet complying with 4.16 and one lavatory complying with 4.19, located adjacent to existing toilet facilities, will be acceptable in lieu of making existing toilet facilities for each sex accessible.

EXCEPTION: In instances of alteration work where provision of a standard stall (Fig. 30(a)) is structurally impracticable or where plumbing code requirements prevent combining existing stalls to provide space, an alternate stall (Fig. 30(b)) may be provided in lieu of the standard stall.

The location of the door is illustrated to be in front of the clear space (next to the water closet), with a maximum stile width of 4 inches (100 mm). An alternate door location is illustrated to be on the side of the toilet stall with a maximum stile width of 4 inches (100 mm). The minimum width of the standard stall shall be 60 inches (1525 mm). The centerline of the water closet shall be 18 inches (455 mm) from the side wall.

Figure 30(a)

Standard Stall

Two alternate stalls are illustrated; one alternate stall is required to be 36 inches (915 mm) in width. The other alternate stall is required to be a minimum of 48 inches (1220 mm) in width. If a wall mounted water closet is used, the depth of the stall is required to be a minimum of 66 inches (1675 mm). If a floor mounted water closet is used, the depth of the stall is required to be a minimum of 69 inches (1745 mm). The 36 inch wide stall shall have parallel grab bars on the side walls. The 48 inch minimum stall shall have a grab bar behind the water closet and one on the side wall next to the water closet. In each alternate, the centerline of the water closet is 18 inches (455 mm) from a side wall.

Figure 30(b)

Alternate Stalls

(f) Assembly areas.

(i) In alterations where it is structurally impracticable to disperse seating throughout the assembly area, seating may be located in collected areas as structurally feasible. Seating shall adjoin an accessible route that also serves as a means of emergency egress.

(ii) In alterations where it is structurally impracticable to alter all performing areas to be on an accessible route, then at least one of each type shall be made accessible.

[MORE INFO...]

*You must sign in to view [MORE INFO...]