6. HEALTH CARE.
6.1 GENERAL.
In addition to the requirements of 4.1 to 4.33, Health Care buildings and facilities shall comply with 6.
6.2 ENTRANCES.
At least one accessible entrance that complies with 4.14 shall be protected from the weather by canopy or roof overhang. Such entrances shall incorporate a passenger loading zone that complies with 4.6.5 (see 4.13.6).
6.3 PATIENT BEDROOMS.
Provide accessible patient bedrooms in compliance with 4. Accessible patient bedrooms shall comply with the following:
(1) Each bedroom shall have a turning space that complies with 4.2.3, and preferably that is located near the entrance.
(2) Each one-bed room shall have a minimum clear floor space of 36 in (915 mm) along each side of the bed, and 42 in (1065 mm) between the foot of the bed and the wall.
(3) Each two-bed room shall have a minimum clear floor space of 42 in (1065 mm), preferably 48 in (1220 mm), between the foot of the bed and the wall; 36 in (915 mm) between the side of the bed and the wall; and 48 in (1220 mm) between beds.
(4) Each four-bed room shall have a minimum clear floor space of 48 in (1220 mm) from the foot of the bed to the foot of the opposing bed; 36 in (915 mm) between the side of the bed and the wall; and 48 in (1220 mm) between beds.
(5) Each bedroom shall have a door that complies with 4.13.
6.4 PATIENT TOILET ROOMS.
Provide each patient bedroom that is required to be accessible with an accessible toilet room that complies with 4.22 or 4.23.