11B-605 URINALS

11B-605.1 General.

Urinals shall comply with Section 11B-605.

[2010 ADAS] Advisory 605.1 General.  Stall-type urinals provide greater accessibility for a broader range of persons, including people of short stature.

11B-605.2 Height and depth.

Urinals shall be the stall-type or the wall-hung type with the rim 17 inches (432 mm) maximum above the finish floor or ground. Urinals shall be 13½ inches (343 mm) deep minimum measured from the outer face of the urinal rim to the back of the fixture.

Figure (a) is an elevation drawing of a wall hung type having the urinal rim 17 inches maximum above the floor with a minimum depth of 13 1/2 inches measured from the outer face of the rim to the back of the fixture.  Figure (b) is an elevation drawing of a stall (floor) type having a minimum depth of 13 1/2 inches measured from the outer face of the rim to the back of the fixture.

FIGURE 11B-605.2

HEIGHT AND DEPTH OF URINALS

11B-605.3 Clear floor space.

A clear floor or ground space complying with Section 11B-305 positioned for forward approach shall be provided.

11B-605.4 Flush controls.

Flush controls shall be hand operated or automatic. Hand operated flush controls shall comply with Section 11B-309 except that the flush control shall be mounted at a maximum height of 44 inches (1118 mm) above the finish floor.

[2010 ADAS] 605.4 Flush Controls.  Flush controls shall be hand operated or automatic. Hand operated flush controls shall comply with 309.