Note: Portions of this document or referenced document qualify for 2013 CBC Section 11B-202.4, Exception 2, and all or part of this information may only apply to California “Safe Harbored” elements addressed in that Exception.

11B-604 WATER CLOSETS AND TOILET COMPARTMENTS

11B-604.1 General.

Water closets and toilet compartments shall comply with Sections 11B-604.2 through 11B-604.8.

Exception:  Water closets and toilet compartments for children's use shall be permitted to comply with Section 11B-604.9.

11B-604.2 Location.

The water closet shall be positioned with a wall or partition to the rear and to one side. The centerline of the water closet shall be 17 inches (432 mm) minimum to 18 inches (457 mm) maximum from the side wall or partition, except that the water closet shall be 17 inches (432 mm) minimum and 19 inches (483 mm) maximum from the side wall or partition in the ambulatory accessible toilet compartment specified in Section 11B-604.8.2. Water closets shall be arranged for a left-hand or right-hand approach. 

[S.H. 1115B.4.1, Item 1]

[2010 ADAS] 604.2 Location.  The water closet shall be positioned with a wall or partition to the rear and to one side. The centerline of the water closet shall be 16 inches (405 mm) minimum to 18 inches (455 mm) maximum from the side wall or partition, except that the water closet shall be 17 inches (430 mm) minimum and 19 inches (485 mm) maximum from the side wall or partition in the ambulatory accessible toilet compartment specified in 604.8.2. Water closets shall be arranged for a left-hand or right-hand approach.

Figure (a) shows a wheelchair accessible water closet, with space on one side, and figure (b) shows an ambulatory accessible water closet, with stall walls and grab bars on both sides. The water closet centerline is shown to be 17 to 18 inches from the side wall in the wheelchair accessible water closet compartment and 17 to 19 inches from the side wall in the ambulatory accessible water closet compartment.

FIGURE 11B-604.2 ‡‡

WATER CLOSET LOCATION

11B-604.3 Clearance.

Clearances around water closets and in toilet compartments shall comply with Section 11B-604.3.

11B-604.3.1 Size.

Clearance around a water closet shall be 60 inches (1524 mm) minimum measured perpendicular from the side wall and 56 inches (1422 mm) minimum measured perpendicular from the rear wall. A minimum 60 inches (1524 mm) wide and 48 inches (1219 mm) deep maneuvering space shall be provided in front of the water closet.

Exception:  In residential dwelling units complying with Section 11B-233.3.1.1, maneuvering space in front of the water closet shall be a minimum 60 inches (1524 mm) wide and 36 inches (914 mm) deep.

[2010 ADAS] 604.3.1 Size.  Clearance around a water closet shall be 60 inches (1525 mm) minimum measured perpendicular from the side wall and 56 inches (1420 mm) minimum measured perpendicular from the rear wall.

ETA Editor's Note

The 2013 CBC 11B-604.3 requirement for clearance in front of accessible water closets exceeds the 2010 ADAS requirement, but a door may swing into the added clearance.

 

The clearance around a water closet is shown in plan view to be 60 inches wide minimum and 56 inches deep minimum with additional maneuvering space in front of the water closet clear floor space, in which a door is permitted to swing over.

FIGURE 11B-604.3.1 ‡‡

SIZE OF CLEARANCE AT WATER CLOSETS

11B-604.3.2 Overlap.

The required clearance around the water closet shall be permitted to overlap the water closet, associated grab bars, dispensers, sanitary napkin disposal units, coat hooks, shelves, accessible routes, clear floor space and clearances required at other fixtures, and the turning space. No other fixtures or obstructions shall be located within the required water closet clearance.

ETA Editor's Note

The Office of Statewide Health Planning and Development (OSHPD), which has jurisdiction over hospitals and long-term care facilities in California, has issued Code Application Notice CAN 2-11B, dated 9/9/14, which includes the following interpretation of Subsection 11B-604.3.2:

Showers are fixtures including a 30 inch x 60 inch clear receptor with a minimum/maximum slope of ¼ inch per foot to a drain (refer to CPC Section 408.5 and CBC Section 11B-608.9), and a threshold, between the shower receptor and the fixture clearance provided outside the shower (CBC Section 11B-608.2.2.1) with a maximum height of ½ inch (CBC Section 11B-608.7).  The required clearance around a water closet may overlap the clearance required outside the shower but not overlap the shower fixture threshold or receptor.

Exception:  In residential dwelling units, a lavatory complying with Section 11B-606 shall be permitted on the rear wall 18 inches (457 mm) minimum from the water closet centerline where the clearance at the water closet is 66 inches (1676 mm) minimum measured perpendicular from the rear wall.

[2010 ADAS] Advisory 604.3.2 Overlap.  When the door to the toilet room is placed directly in front of the water closet, the water closet cannot overlap the required maneuvering clearance for the door inside the room.
The clearance around a water closet is shown in plan view to be 60 inches wide minimum and 66 inches deep minimum with a lavatory permitted on the real wall if the distance between the lavatory nearest edge and the water closet center line is 18 inches minimum.

FIGURE 11B-604.3.2 (EXCEPTION)

OVERLAP OF WATER CLOSET CLEARANCE IN RESIDENTIAL DWELLING UNITS

11B-604.4 Seats.

The seat height of a water closet above the finish floor shall be 17 inches (432 mm) minimum and 19 inches (483 mm) maximum measured to the top of the seat. Seats shall not be sprung to return to a lifted position. Seats shall be 2 inches (51 mm) high maximum.

[2010 ADAS] 604.4 Seats.  The seat height of a water closet above the finish floor shall be 17 inches (430 mm) minimum and 19 inches (485 mm) maximum measured to the top of the seat. Seats shall not be sprung to return to a lifted position.

Exceptions:

1.      Reserved.

[2010 ADAS] 1.  A water closet in a toilet room for a single occupant accessed only through a private office and not for common use or public use shall not be required to comply with 604.4.

2.      In residential dwelling units, the height of water closets shall be permitted to be 15 inches (381 mm) minimum and 19 inches (483 mm) maximum above the finish floor measured to the top of the seat.

3.      A 3-inch (76 mm) high seat shall be permitted only in alterations where the existing fixture is less than 15 inches (381 mm) high.

11B-604.5 Grab bars.

Grab bars for water closets shall comply with Section 11B-609. Grab bars shall be provided on the side wall closest to the water closet and on the rear wall. Where separate grab bars are required on adjacent walls at a common mounting height, an L-shaped grab bar meeting the dimensional requirements of Sections 11B-604.5.1 and 11B-604.5.2 shall be permitted.

[2010 ADAS] 604.5 Grab Bars.  Grab bars for water closets shall comply with 609. Grab bars shall be provided on the side wall closest to the water closet and on the rear wall.

Exceptions:

1.      Reserved.

[2010 ADAS] 1.  Grab bars shall not be required to be installed in a toilet room for a single occupant accessed only through a private office and not for common use or public use provided that reinforcement has been installed in walls and located so as to permit the installation of grab bars complying with 604.5.

2.      In residential dwelling units, grab bars shall not be required to be installed in toilet or bathrooms provided that reinforcement has been installed in walls and located so as to permit the installation of grab bars complying with Section 11B-604.5.

[2010 ADAS] Advisory 604.5 Grab Bars Exception 2.  Reinforcement must be sufficient to permit the installation of rear and side wall grab bars that fully meet all accessibility requirements including, but not limited to, required length, installation height, and structural strength.

3.      In detention or correction facilities, grab bars shall not be required to be installed in housing or holding cells that are specially designed without protrusions for purposes of suicide prevention.

11B-604.5.1 Side wall.

The side wall grab bar shall be 42 inches (1067 mm) long minimum, located 12 inches (305 mm)  maximum from the rear wall and extending 54 inches (1372 mm) minimum from the rear wall with the front end positioned 24 inches (610 mm) minimum in front of the water closet.

[2010 ADAS] 604.5.1 Side Wall.  The side wall grab bar shall be 42 inches (1065 mm) long minimum, located 12 inches (305 mm) maximum from the rear wall and extending 54 inches (1370 mm) minimum from the rear wall.

Elevation drawing shows the side wall grab bar to be 42 inches long minimum, located 12 inches maximum from the rear wall, 24" in front of the water closet, and extending 54 inches minimum from the rear wall.

FIGURE 11B-604.5.1 ‡‡

SIDE WALL GRAB BAR AT WATER CLOSETS

ETA Editor's Note

At Hospital toilets and bathrooms used by patients, the 2013 California Electrical Code (2013 CEC) requires a nurse call device at the side wall of a water closet that must be coordinated carefully with the side grab bar at an accessible water closet to ensure that accessible clearances are met.  The following excerpts are from the 2013 CEC Errata dated January 1, 2014:

         517.123 [OSHPD 1, 2, 3 & 4] Call Systems.  Hospital signaling and nurse call equipment includes four types of call stations:  patient stations, bath stations, staff emergency stations, and code call stations.

                  (A) General.  ...

                  (B) Patient Stations.  ...

                  (C) Bath Stations.  A bath station that can be activated by a patient lying on the floor shall be provided at each room containing a patient water closet, bathtub, sitz bath, or shower stall. Pull cords shall extend to a maximum of 12 inches (30.48 centimeters) above the floor.

                           (1) An alarm in these areas shall be able to be turned off only at the bath station where it was initiated.

                                    Exception:  When two or more stations are located in the same bath area and all are visible from any call location, the alarm may be canceled at any of these locations.

                           (2) Bath stations in shower stalls and tubs shall be located 5 to 6 feet (1.52 to 1.83 meters) above the floor, within normal view of the user and within reach of staff without the need to step into the stall or tub.

                           (3) Bath stations shall be located to the side of toilets, within 12 inches (30.48 centimeters) of the front of the toilet bowl and 3 to 4 feet (.91 meter to 1.22 meters) above the floor. A bath station shall be permitted to serve both a toilet and a shower or other fixture if it is accessible to both.

                  (D) Staff Emergency Stations.  ...

                  (E) Code Call Stations.  ...

At 517.123(C)(3), the height of the nurse call device is not specified to be measured to the top of the box, as it is at 2013 CBC 11B-308.1.1 for electrical switches and 11B-308.1.2 for electrical receptacles.  It is recommended to install the nurse call device at/near the high limit of the allowable range, maintaining 12" minimum clearance above the top of the side grab bar, thus complying with 2013 CBC 11B-609.3.

Although the requirements of 2013 CEC 517.123 apply specifically to Hospitals and other facilities under OSHPD jurisdiction, it is not uncommon for nurse call devices to be installed at patient toilets in medical office buildings that are not under OSHPD jurisdiction.  In these, the positioning of the nurse call device is not strictly regulated by Code, but accessible clearances must be maintained from the grab bars at accessible water closets.

11B-604.5.2 Rear wall.

The rear wall grab bar shall be 36 inches (914 mm) long minimum and extend from the centerline of the water closet 12 inches (305 mm) minimum on one side and 24 inches (610 mm) minimum on the other side.

Exceptions:

1.      The rear grab bar shall be permitted to be 24 inches (610 mm) long minimum, centered on the water closet, where wall space does not permit a length of 36 inches (914 mm) minimum due to the location of a recessed fixture adjacent to the water closet.

2.      Where an administrative authority requires flush controls for flush valves to be located in a position that conflicts with the location of the rear grab bar, then the rear grab bar shall be permitted to be split or shifted to the open side of the toilet area.

ETA Editor's Note

The Office of Statewide Health Planning and Development (OSHPD), which has jurisdiction over hospitals and long-term care facilities in California, has issued Code Application Notice CAN 2-11B, dated 9/9/14, which includes the following interpretation of Subsection 11B-604.5.2:

CBC Section 1224.14.2.7 requires the provision of a flushing-rim clinical sink in the soiled utility room of a nursing unit.  There is an allowance to eliminate the clinical sink if facilities for cleaning bedpans are provided elsewhere.  CPC Table 4-2 Footnote 14 allows the clinical sink to be deleted if all bedrooms in the nursing unit are provided with adjoining toilets with bedpan flushing devices.

Patient toilet rooms with bedpan flushing devices are an allowance, not a requirement.  If this approach is pursued, the bedpan flushing device shall not be a unit that results in the need to split or offset the rear grab bar.  Section 11B-604.5.2 is not available to accommodate bedpan flushing devices.  The gripping surface of the grab bar must be available for the entire 36-inch length without interruption.

Bedpan washing devices that are manufactured as part of a flush valve assembly project above the rear grab bar, obstructing it.  OSHPD's interpretation disallows those at the water closets in accessible Patient Toilets.  There are wall-mounted bedpan washing devices that could be used instead, taking care not to obstruct either the side or the rear grab bars, or the required clear floor space.

 

Elevation drawing shows the rear grab bar 36 inches long minimum, positioned so that 24 inches minimum extends toward the open transfer side and 12 inches minimum extends toward the side wall.

FIGURE 11B-604.5.2

REAR WALL GRAB BAR AT WATER CLOSETS

11B-604.6 Flush controls.

Flush controls shall be hand operated or automatic. Hand operated flush controls shall comply with Section 11B-309 except they shall be located 44 inches (1118 mm) maximum above the floor. Flush controls shall be located on the open side of the water closet except in ambulatory accessible compartments complying with Section 11B-604.8.2.

[2010 ADAS] 604.6 Flush Controls.  Flush controls shall be hand operated or automatic. Hand operated flush controls shall comply with 309. Flush controls shall be located on the open side of the water closet except in ambulatory accessible compartments complying with 604.8.2.

[2010 ADAS] Advisory 604.6 Flush Controls.  If plumbing valves are located directly behind the toilet seat, flush valves and related plumbing can cause injury or imbalance when a person leans back against them. To prevent causing injury or imbalance, the plumbing can be located behind walls or to the side of the toilet; or if approved by the local authority having jurisdiction, provide a toilet seat lid.

11B-604.7 Dispensers.

Toilet paper dispensers shall comply with Section 11B-309.4 _|Operation|_ and shall be 7 inches (178 mm) minimum and 9 inches (229 mm) maximum in front of the water closet measured to the centerline of the dispenser. The outlet of the dispenser shall be below the grab bar, 19 inches (483 mm) minimum above the finish floor and shall not be located behind grab bars. Dispensers shall not be of a type that controls delivery or that does not allow continuous paper flow. 

[S.H. 1115B.8.4]

[2010 ADAS] 604.7 Dispensers. Toilet paper dispensers shall comply with 309.4 and shall be 7 inches (180 mm)  minimum and 9 inches (230 mm)  maximum in front of the water closet measured to the centerline of the dispenser. The outlet of the dispenser shall be 15 inches (380 mm) minimum and 48 inches (1220 mm) maximum above the finish floor and shall not be located behind grab bars. Dispensers shall not be of a type that controls delivery or that does not allow continuous paper flow.

Elevation drawing shows the centerline of the toilet paper dispenser to be 7 to 9 inches in front of the water closet. The outlet of the dispenser is shown below the grab bar at 19" minimum above the floor.

FIGURE 11B-604.7 ‡‡

DISPENSER OUTLET LOCATION

11B-604.8 Toilet compartments.

Wheelchair accessible toilet compartments shall meet the requirements of Sections 11B-604.8.1 and 11B-604.8.3 _|Coat Hooks and Shelves|_. Compartments containing more than one plumbing fixture shall comply with Section 11B-603. Ambulatory accessible compartments shall comply with Sections 11B-604.8.2 and 11B-604.8.3.

11B-604.8.1 Wheelchair accessible compartments.

Wheelchair accessible compartments shall comply with Section 11B-604.8.1.

11B-604.8.1.1 Size.

Wheelchair accessible compartments shall be 60 inches (1524 mm) wide minimum measured perpendicular to the side wall, and 56 inches (1422 mm) deep minimum for wall hung water closets and 59 inches (1499 mm) deep minimum for floor mounted water closets measured perpendicular to the rear wall. Wheelchair accessible compartments shall additionally provide maneuvering space complying with Section 11B-604.8.1.1.1, 11B-604.8.1.1.2, or 11B-604.8.1.1.3, as applicable. Wheelchair accessible compartments for children’s use shall be 60 inches (1524 mm) wide minimum measured perpendicular to the side wall, and 59 inches (1499 mm) deep minimum for wall hung and floor mounted water closets measured perpendicular to the rear wall.

[2010 ADAS] Advisory 604.8.1.1 Size.  The minimum space required in toilet compartments is provided so that a person using a wheelchair can maneuver into position at the water closet. This space cannot be obstructed by baby changing tables or other fixtures or conveniences, except as specified at 604.3.2 (Overlap). If toilet compartments are to be used to house fixtures other than those associated with the water closet, they must be designed to exceed the minimum space requirements. Convenience fixtures such as baby changing tables must also be accessible to people with disabilities as well as to other users. Toilet compartments that are designed to meet, and not exceed, the minimum space requirements may not provide adequate space for maneuvering into position at a baby changing table.
11B-604.8.1.1.1 Maneuvering space with in-swinging door.

In a wheelchair accessible compartment with an in-swinging door, a minimum 60 inches (1524 mm) wide by 36 inches (914 mm) deep maneuvering space shall be provided in front of the clearance required in Section 11B-604.8.1.1. See Figures 11B-604.8.1.1.2 (b) and 11B-604.8.1.1.3 (b).

11B-604.8.1.1.2 Maneuvering space with side-opening door .

In a wheelchair accessible compartment with a door located in the side wall or partition, either in-swinging or out-swinging, a minimum 60 inches (1524 mm) wide and 60 inches (1524 mm) deep maneuvering space shall be provided in front of the water closet. See Figure 11B-604.8.1.1.2.

Plan drawing of a wheelchair accessible compartment with a side opening door, showing required width and depth dimensions, including the additional maneuvering space required inside the compartment when an inswinging door is used

FIGURE 11B-604.8.1.1.2 ‡‡

MANEUVERING SPACE WITH SIDE-OPENING DOOR

11B-604.8.1.1.3 Maneuvering space with end-opening door.

In a wheelchair accessible compartment with a door located in the front wall or partition (facing the water closet), either in-swinging or out-swinging, a minimum 60 inches (1524 mm) wide and 48 inches (1219 mm) deep maneuvering space shall be provided in front of the water closet. See Figure 11B-604.8.1.1.3.

Plan drawing of a wheelchair accessible compartment with an end opening door, showing required width and depth dimensions, including an additional maneuvering space required inside the compartment when an inswinging door is used

FIGURE 11B-604.8.1.1.3 ‡‡

MANEUVERING SPACE WITH END-OPENING DOOR

11B-604.8.1.2 Doors.

Toilet compartment doors, including door hardware, shall comply with Section 11B-404 except that if the approach is from the push side of the compartment door, clearance between the door side of the compartment and any obstruction shall be 48 inches (1219 mm) minimum measured perpendicular to the compartment door in its closed position. Doors shall be located in the front partition or in the side wall or partition farthest from the water closet. Where located in the front partition, the door opening shall be 4 inches (102 mm) maximum from the side wall or partition farthest from the water closet. Where located in the side wall or partition, the door opening shall be 4 inches (102 mm) maximum from the front partition. The door shall be self-closing. A door pull complying with Section 11B-404.2.7 shall be placed on both sides of the door near the latch.  Doors shall not swing into the clear floor space or clearance required for any fixture. Doors may swing into that portion of maneuvering space which does not overlap the clearance required at a water closet.

[2010 ADAS] 604.8.1.2 Doors.  Toilet compartment doors, including door hardware, shall comply with 404 except that if the approach is to the latch side of the compartment door, clearance between the door side of the compartment and any obstruction shall be 42 inches (1065 mm)  minimum. Doors shall be located in the front partition or in the side wall or partition farthest from the water closet. Where located in the front partition, the door opening shall be 4 inches (100 mm) maximum from the side wall or partition farthest from the water closet. Where located in the side wall or partition, the door opening shall be 4 inches (100 mm) maximum from the front partition. The door shall be self-closing. A door pull complying with 404.2.7 shall be placed on both sides of the door near the latch. Toilet compartment doors shall not swing into the minimum required compartment area.

Exception:  When located at the side of a toilet compartment, the toilet compartment door opening shall provide a clear width of 34 inches (864 mm) minimum.

DSA icon
Advisory 11B-604.8.1.2 Doors. This item describes requirements pertaining to the accessible water closet compartment door and the route to the door.

The door is required to have a latch which is flip-over style, sliding or which otherwise does not require the user to grasp or twist.  This is to facilitate latching the door by people with limited hand or finger dexterity.

The last part of this item addresses the required maneuvering space at the compartment door. This space is required to comply with requirements for door maneuvering space in Section 11B-404.2.4, except the space in front of the door shall be no less than 48 inches deep, measured perpendicular to the closed door. Where Figure 11B-404.2.4.1 (f) and  (j), specifically allow a 44” minimum maneuvering space perpendicular to doors in general in the closed position, a minimum of 48” must be provided in order to comply with Section 11B-604.8.1.2.

Note that in Figure 11B-404.2.4.1 (c) the front approach requires 12 inches of strike-side clearance on the push side where a door has both a latch and a closer.  However, the US Department of Justice has indicated that a self-closing compartment door with a gravity hinge is not considered to be a door with a closer; hence the 12-inch clearance would not be required in this type of design. ◼

ETA Editor's Note

For wheelchair accessible compartments with in-swinging doors, the compartment size required by CBC is nominally the same as required by 2010 ADAS.  For compartments with out-swinging doors, 2013 CBC requires larger compartments than 2010 ADAS due to the 48” minimum maneuvering space required in front of the water closet by 11B-604.8.1.1.3.

 

The compartment door is hinged 4 inches maximum from the side wall or partition farthest from the water closet so that the door opens on to the open transfer space. The minimum clearance between the door side of the stall and any obstruction is 42 inches.
Plan drawing of a wheelchair accessible compartment. The compartment door is hinged 4" maximum from the corner opposite the water closet. The compartment door swings out and is shown at the end of the stall with an alternate door location shown on the side of the compartment opposite the side wall with the grab bar.

FIGURE 11B-604.8.1.2

WHEELCHAIR ACCESSIBLE TOILET COMPARTMENT DOORS

11B-604.8.1.3 Approach.

Compartments shall be arranged for left-hand or right-hand approach to the water closet.

11B-604.8.1.4 Toe clearance.

At least one side partition shall provide a toe clearance of 9 inches (229 mm) minimum above the finish floor and 6 inches (152 mm) deep minimum beyond the compartment-side face of the partition, exclusive of partition support members. Partition components at toe clearances shall be smooth without sharp edges or abrasive surfaces. Compartments for children’s use shall provide a toe clearance of 12 inches (305 mm) minimum above the finish floor.  [S.H.:  Previous editions of CBC did not require toe clearance at accessible toilet compartments, since the minimum size allowed for these compartments would qualify them for the exemption at 1991 ADAAG 4.17.4.]

[2010 ADAS] 604.8.1.4 Toe Clearance.  The front partition and at least one side partition shall provide a toe clearance of 9 inches (230 mm) minimum above the finish floor and 6 inches (150 mm) deep minimum beyond the compartment-side face of the partition, exclusive of partition support members. Compartments for children’s use shall provide a toe clearance of 12 inches (305 mm) minimum above the finish floor.

Exception:  Toe clearance at the side partition is not required in a compartment greater than 66 inches (1676 mm) wide.

[2010 ADAS] EXCEPTION:  Toe clearance at the front partition is not required in a compartment greater than 62 inches deep with a wall-hung water closet or 65 inches deep with a floor-mounted water closet. Toe clearance at the side partition is not required in a compartment greater than 66 inches (1675 mm) wide. Toe clearance at the front partition is not required in a compartment for children’s use that is greater than 65 inches deep.

Figure (a) is an elevation drawing showing toe clearance under a toilet compartment partition. Toe clearance is 9 inches high minimum and 6 inches deep minimum beyond the compartment-side face of the partition. Figure (b) is an elevation drawing for a children’s toilet compartment. Toe clearance is 12 inches high minimum and 6 inches deep minimum beyond the compartment-side face of the partition. Figure (c) is a plan view showing toe clearance under the front partition and one side partition, 6 inches deep minimum.

FIGURE 11B-604.8.1.4

WHEELCHAIR ACCESSIBLE TOILET COMPARTMENT TOE CLEARANCE

11B-604.8.1.5 Grab bars.

Grab bars shall comply with Section 11B-609. A side-wall grab bar complying with Section 11B-604.5.1 shall be provided and shall be located on the wall closest to the water closet. In addition, a rear-wall grab bar complying with Section 11B-604.5.2 shall be provided. Where separate grab bars are required on adjacent walls at a common mounting height, an L-shaped grab bar meeting the dimensional requirements of Sections 11B-604.5.1 and 11B-604.5.2 shall be permitted.

[2010 ADAS] 604.8.1.5 Grab Bars.  Grab bars shall comply with 609. A side-wall grab bar complying with 604.5.1 shall be provided and shall be located on the wall closest to the water closet. In addition, a rear-wall grab bar complying with 604.5.2 shall be provided.

ETA Editor's Note

See the ETA Editor's Note following Figure 11B-604.5.1 pertaining to the coordination of nurse call devices with side grab bars at accessible water closets in Hospitals and other facilities under OSHPD jurisdiction.

11B-604.8.2 Ambulatory accessible compartments.

Ambulatory accessible compartments shall comply with Section 11B-604.8.2.

11B-604.8.2.1 Size.

Ambulatory accessible compartments shall have a depth of 60 inches (1524 mm) minimum and a width of 35 inches (889 mm) minimum and 37 inches (940 mm) maximum.

11B-604.8.2.2 Doors.

Toilet compartment doors, including door hardware, shall comply with Section 11B-404, except that if the approach is to the latch side of the compartment door, clearance between the door side of the compartment and any obstruction shall be 44 inches (1118 mm) minimum. The door shall be self-closing. A door pull complying with Section 11B-404.2.7 shall be placed on both sides of the door near the latch. Toilet compartment doors shall not swing into the minimum required compartment area.

[S.H. 1115B.3.1, Item 5]
11B-604.8.2.3 Grab bars.

Grab bars shall comply with Section 11B-609. A side-wall grab bar complying with Section 11B-604.5.1 shall be provided on both sides of the compartment.

The compartment is 60 inches deep minimum and 35 to 37 inches wide, with grab bars on both sides. The minimum clearance between the door side of the stall and any obstruction is 44 inches.

FIGURE 11B-604.8.2 ‡‡

AMBULATORY ACCESSIBLE TOILET COMPARTMENT

11B-604.8.3 Coat hooks and shelves.

Coat hooks shall be located within one of the reach ranges specified in Section 11B-308. Shelves shall be located 40 inches (1016 mm) minimum and 48 inches (1219 mm) maximum above the finish floor. [S.H.: For coat hooks, see Safe Harbor at Subsections 11B-308.3.1 & 11B-308.3.2] For shelves, see [S.H. 1125B.3].

11B-604.9 Water closets and toilet compartments for children's use.

Water closets and toilet compartments for children's use shall comply with Section 11B-604.9.

[2010 ADAS] Advisory 604.9 Water Closets and Toilet Compartments for Children's Use.  The requirements in 604.9 are to be followed where the exception for children's water closets in 604.1 is used. The following table provides additional guidance in applying the specifications for water closets for children according to the age group served and reflects the differences in the size, stature, and reach ranges of children ages 3 through 12. The specifications chosen should correspond to the age of the primary user group. The specifications of one age group should be applied consistently in the installation of a water closet and related elements. 

TABLE 11B-604.9

SUGGESTED DIMENSIONS FOR CHILDREN’S USE

SUGGESTED DIMENSIONS FOR WATER CLOSETS SERVING CHILDREN AGES 3 THROUGH 12

 

Ages 3 and 4

Ages 5 through 8

Ages 9 through 12

Water Closet Centerline

12 inches (305 mm)

12 to 15 inches (305 to 381 mm)

15 to 18 inches (381 to 457 mm)

Toilet Seat Height

11 to 12 inches (279 to 305 mm)

12 to 15 inches (305 to 381 mm)

15 to 17 inches (381 to 432 mm)

Grab Bar Height

18 to 20 inches (457 to 508 mm)

20 to 25 inches (508 to 635 mm)

25 to 27 inches (635 to 686 mm)

Dispenser Height

14 inches (356 mm)

14 to 17 inches (356 to 432 mm)

17 to 19 inches (432 to 483 mm)

11B-604.9.1 Location.

The water closet shall be located with a wall or partition to the rear and to one side. The centerline of the water closet shall be 12 inches (305 mm) minimum and 18 inches (457 mm) maximum from the side wall or partition, except that the water closet shall be 17 inches (432 mm) minimum and 19 inches (483 mm) maximum from the side wall or partition in the ambulatory accessible toilet compartment specified in Section 11B-604.8.2. Compartments shall be arranged for left-hand or right-hand approach to the water closet.

11B-604.9.2 Clearance.

Clearance around a water closet shall comply with Section 11B-604.3.

11B-604.9.3 Height.

The height of water closets shall be 11 inches (279 mm) minimum and 17 inches (432 mm) maximum measured to the top of the seat. Seats shall not be sprung to return to a lifted position.

11B-604.9.4 Grab bars.

Grab bars for water closets shall comply with Section 11B-604.5.

11B-604.9.5 Flush controls.

Flush controls shall be hand operated or automatic. Hand operated flush controls shall comply with Sections 11B-309.2 and 11B-309.4 and shall be installed 36 inches (914 mm) maximum above the finish floor. Flush controls shall be located on the open side of the water closet except in ambulatory accessible compartments complying with Section 11B-604.8.2.

11B-604.9.6 Dispensers.

Toilet paper dispensers shall comply with Section 11B-309.4 _|Operation|_ and shall be 7 inches (178 mm) minimum and 9 inches (229 mm) maximum in front of the water closet measured to the centerline of the dispenser. The outlet of the dispenser shall be 14 inches (356 mm) minimum and 19 inches (483 mm) maximum above the finish floor. There shall be a clearance of 1½ inches (38 mm) minimum below the grab bar. Dispensers shall not be of a type that controls delivery or that does not allow continuous paper flow.

11B-604.9.7 Toilet Compartments.

Toilet compartments shall comply with Section 11B-604.8.

[MORE INFO...]