11B-206.4.1 Entrances and exterior ground floor exits.
All entrances and exterior ground-floor exits to buildings and facilities shall comply with Section 11B-404.
[2010 ADAS] 206.4.1 Public Entrances. In addition to entrances required by 206.4.2 through 206.4.9, at least 60 percent of all public entrances shall comply with 404.
Exceptions:
1. Exterior ground floor exits serving smoke-proof enclosures, stairwells, and exit doors serving stairs only shall not be required to comply with Section 11B-404.
2. Exits in excess of those required by Chapter 10, and which are more than 24 inches (610 mm) above grade shall not be required to comply with Section 11B-404. Directional signs shall comply with Chapter 10, Section 1007.10.
ETA Editor's Note
The ADA requirements included at Subsection 11B-206.4.1 are provided for information. While the CBC scoping requirements are more inclusive in most cases, there are rare scenarios under which the ADA scoping requirements become more inclusive (e.g., if more than 40 percent of Public Entrances are more than 24 inches above grade).