[F] 907.5.2.3.1 Public and common use areas.
Visible alarm notification appliances shall be provided in public use areas and common use areas, including but not limited to:
-
Band rooms
-
Classrooms
-
Corridors
-
Gymnasiums
-
Lobbies
-
Meeting rooms
-
Multipurpose rooms
-
Music practice rooms
-
Occupational shops
-
Occupied rooms where ambient noise impairs hearing of the fire alarm
-
Sanitary facilities including restrooms, bathrooms and shower rooms
Exception: Where employee work areas have audible alarm coverage, the notification appliance circuits serving the employee work areas shall be initially designed with not less than 20-percent spare capacity to account for the potential of adding visible notification appliances in the future to accommodate hearing-impaired employee(s).
Advisory 907.5.2.3.1 Public and common use areas. This list is not exhaustive. In new construction, all public- and common-use areas shall have visible alarms if audible alarms are provided.◼