[F] 907.5.2.3.2 Groups R-1 and R-2.1. Group R-1 and R-2.1 dwelling units or sleeping units in accordance with Table 907.5.2.3.2 shall be provided with a visible alarm notification appliance, activated by both the in-room smoke alarm and the building fire alarm system.
[F] TABLE 907.5.2.3.2 VISIBLE ALARMS
NUMBER OF SLEEP UNITS | SLEEPING ACCOMMODATIONS WITH VISIBLE ALARMS |
6 to 25 | 2 |
26 to 50 | 4 |
51 to 75 | 7 |
76 to 100 | 9 |
101 to 150 | 12 |
151 to 200 | 14 |
201 to 300 | 17 |
301 to 400 | 20 |
401 to 500 | 22 |
501 to 1,000 | 5% of total |
1,001 and over | 50 plus 3 for each 100 over 1,000 |
[SFM] Also see Chapter 11B, Section 11B-224.4 and Table 11B-224.4.