[F] 907.5.2.3.2 Groups R-1 and R-2.1.

Habitable spaces in dwelling units and sleeping units in Group R-1 and R-2.1 occupancies in accordance with Table 907.5.2.3.2 shall be provided with visible alarm notification. Visible alarms shall be activated by the in-room smoke alarm and the building fire alarm system.

[F] TABLE 907.5.2.3.2 VISIBLE ALARMS

NUMBER OF SLEEP UNITS

SLEEPING ACCOMMODATIONS WITH VISIBLE ALARMS

6 to 25

2

26 to 50

4

51 to 75

7

76 to 100

9

101 to 150

12

151 to 200

14

201 to 300

17

301 to 400

20

401 to 500

22

501 to 1,000

5% of total

1,001 and over

50 plus 3 for each 100 over 1,000

[SFM] Also see Chapter 11B, Section 11B-224.4 and Table 11B-224.4.