Note: This excerpt is only a portion of a larger, Referenced Standards document and out of context may not include all information needed for use. Also, it may not reflect the most current building code requirements. The Referenced Standard, in its entirety, may be available for purchase from the International Code Council at http://shop.iccsafe.org.

1003.2.13.2 Enclosed stairways.

An enclosed stairway, to be considered part of an accessible means of egress, shall have a clear width of 48 inches (1219 mm) minimum between handrails and shall either incorporate an area of refuge within an enlarged floor-level landing or shall be accessed from either an area of refuge complying with Section 1003.2.13.5 or a horizontal exit.

Exceptions:

1. Stairways serving a single guestroom or dwelling unit.

2.  Stairways in buildings or facilities equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2.

3. The clear width of 48 inches (1219 mm) between handrails is not required for enclosed stairways accessed from a horizontal exit.

4. Stairways serving open parking garages.