Other Requirements in the ADA Standards
Platform Lifts
Platform lifts, where permitted on an accessible means of egress, must have standby power (§207.2).
Fire Alarm Systems
Where fire alarms systems are provided, they must meet requirements for audible and visual features in the ADA Standards and the referenced NFPA 72 Fire Alarm Code (§215).
Operable Parts
Operable parts used by building occupants, including alarms pulls and hardware for fire extinguisher cabinets, must comply (§205, §309). They must be usable with one hand and without tight grasping, pinching, or twisting of the wrist, or more than 5 pounds of force. Non-fixed elements, such as fire extinguishers, are not subject to the ADA Standards.
Automated Doors
Maneuvering clearance is required on the egress side of automated doors unless they are equipped with standby power or they stay open in power-off mode (§404.3.2). The standards also require a minimum 32” break out opening for doors unless equipped with standby power or a compliant manual swinging door also serves the same means of egress (§404.3.6).