11B-605 Urinals

11B-605.1 General.

Urinals shall comply with Section 11B-605.

DOJ icon
Advisory 11B-605.1 General. Stall-type urinals provide greater accessibility for a broader range of persons, including people of short stature.

11B-605.2 Height and depth.

Urinals shall be the stall-type or the wall-hung type with the rim 17 inches (432 mm) maximum above the finish floor or ground. Urinals shall be 13½ inches (343 mm) deep minimum measured from the outer face of the urinal rim to the back of the fixture.

Figure (a) is an elevation drawing of a wall hung type having the urinal rim 17 inches maximum above the floor with a minimum depth of 13 1/2 inches measured from the outer face of the rim to the back of the fixture.

(a) wall hung type

Figure (b) is an elevation drawing of a stall (floor) type having a minimum depth of 13 1/2 inches measured from the outer face of the rim to the back of the fixture.

(b) stall type

FIGURE 11B-605.2 HEIGHT AND DEPTH OF URINALS

11B-605.4 Flush controls.

Flush controls shall be hand operated or automatic. Hand operated flush controls shall comply with Section 11B-309 except that the flush control shall be mounted at a maximum height of 44 inches (1118 mm) above the finish floor.

[2010 ADA Standards] 605.4 Flush Controls. Flush controls shall be hand operated or automatic. Hand operated flush controls shall comply with 309.